| Plan Review Notes For Permit 00040991 |
| Permit Number |
00040991 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************** UNSAT ****************** | | | | | | 1)NOTE: NEED TO SHOW DETAIL ON ALL THE | | | ELECTRICAL WORK BEING DONE. | | | PLEASE GIVE IN DETAILS. | | | PLEASE SUBMIT THE SIZE OF THE EXISTING | | | SERVICE. | | | | | | 2)NOTE: AS PER 210-11-C-3 BATH(S) REQ` | | | A SEPARATE 20 AMP CIRCUIT #12 AWG. | | | | | | 3)ALSO OUTLET SPACING TO MEET CODE ON | | | INTERIOR WALLS. | | | | | | 4)NOTE: MEANS OF EGRESS LIGHTING FOR | | | EACH ROOM 210-70 | | | | | | 5)NOTE: SMOKE DETECTORS ARE GOING TO BE | | | REQ`D INSDIE AND OUTSIDETHE BEDROOM. | | | NFPA-72 2-2.1.1.1 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. 659-8096 EXT 8372 |
|