| 2001-01-08 00:00:00 | SUBMIT SQ.FOOTAGE OF HABITABLE FLOOR |
| | SPACE TO ENSURE COMPLIANCE W/TABLE 407 |
| | OF SPC 1994 EDITION.REFER TO SEC.407.1.3 |
| | FOR ALLOWED DEDUCTIBLE AREAS. |
| | |
| | PLANS SHALL BEAR CITY PLACE LANDLORD |
| | APPROVAL STAMPS. |
| | |
| | SINK AT KITCHEN AREA SHALL COMPLY W/ |
| | FACBC SECS.4.24.1-4.24.7. |
| | |
| | SANITARY FACILITIES AND DRINKING |
| | FOUNTAIN SHALL BE ACCESSIBLE TO THE |
| | PUBLIC PER SPC SEC.407.2.2. |
| | |
| | DRINKING FOUNTAIN SHALL COMPLY W/FACBC |
| | SEC.4.1.3.(10)(A),4.15.PROVISIONS SHALL |
| | BE MADE FOR PERSONS WHO HAVE TROUBLE |
| | BENDING OR STOOPING.SUBMIT DETAIL. |
| | |
| | SHOW DIMENSIONS OF TOILET ROOMS.SIZE AND |
| | CLEAR FLOOR SPACE FOR FIXTURES SHALL |
| | COMPLY W/FACBC SEC.4.16,FIG.28. |
| | |
| | SHT.A-17-LENGTH OF GRAB BARS BEHIND AND |
| | ALONG SIDE WATER CLOSETS SHALL COMPLY |
| | W/FACBC SECS.4.16.4,FIG.#29. |
| | |
| | HEIGHT OF TOWEL DISPENSERS SHALL COMPLY |
| | W/FACBC SEC.4.2.5, 4.2.6. |
| | |
| | SHOW HEIGHT OF H.C.WATER CLOSET.COMPLY |
| | W/FACBC SEC.4.16.3. |
| | |
| | CLEAR FLOOR SPACE UNDER H.C.LAV.SHALL |
| | COMPLY W/FACBC SEC.4.19.2. |
| | |
| | WATER HEATER SHALL BE READILY ACCESSIBLE |
| | PER SPC SEC.501.7.PROVIDE FIXED LADDER |
| | OR RELOCATE TO FLOOR. |
| | |
| | SUBMIT MANUF.SHEETS FOR STEAMERS.MAX. |
| | TEMP.OF WATER TO SANITARY SHALL BE 140 |
| | DEGREES PER SPC SEC.717.8. |