| 2001-01-08 00:00:00 | *************DENIED********************* | | | | | | 1) EXHAUST FANS NOTE 2 SHOW VENT TO | | | ABOVE CEILING SPACE. 1997 SMC 501.3 | | | REQUIRES ALL EXHAUST TO BE DISCHARGED | | | OUTDOORS. | | | 2) SAFE ROOM SHOWS NO VENTILATION. | | | 1997 SMC 403 REQUIRES EVERY PORTION OF | | | EVERY BUILDING TO BE VENTILATED IN | | | ACCORDANCE WITH ASHRAE 62-89 | | | 3) DIFFUSER DETAIL INDICATES FLEX | | | ATTACHMENT METHOD. NOTE METHOD TO COMPLY | | | WITH ENERGY EFFICIENCY CODE FOR BLDG | | | CONSTRUCTION 1997 410.1ABCD.3.3 |
|