| Date |
Text |
| 2001-01-08 00:00:00 | FLOOR DRAINS ARE REQD.IN THE COMMON |
| | LAUNDRY ROOMS PER SPC SEC.409.4.5. |
| | |
| | PLUMBING DRAWINGS SHOW A 2"PD LINE |
| | REDUCING TO 1 1/2".CLARIFY. |
| | |
| | SHT.DAPT-P5.01-TUBS LOCATED DOWNSTREAM |
| | OF WATER CLOSETS SHALL BE VENTED PER SPC |
| | 913.2. |
| | |
| | ALL BATHROOMS IN THE DWELLING UNIT SHALL |
| | COMPLY W/THE PROVISIONS OF THE FEDERAL |
| | FAIR HOUSING ACT 24 CFR 100.205 (C)(3) |
| | (IV),REQ.#7(2),PARAGRAPH (A) OR (B). |
| | INDICATE ON THE PLANS WHICH DESIGN |
| | OPTION (A OR B) IS BEING USED. |
| | |
| | COMMON AREA LAUNDRY ROOMS SHALL COMPLY |
| | W/FEDERAL FAIR HOUSING ACT REQ.#3(USABLE |
| | DOORS),AND ANSI SEC.4.32.6. |
| | |
| | CLEAR SPACE OF 30"WIDE SHALL BE PROVIDED |
| | BETWEEN FRONT OF TOILET BOWL AND WALL |
| | TO PROVIDE PERPENDICULAR APPROACH TO TUB |
| | IF FHA DESIGN OPTION "A"IS USED. |
| | |
| | DOORS IN BATHROOMS SHALL NOT SWING INTO |
| | CLEAR FLOOR SPACE REQD.FOR ANY FIXTURE. |
| | SHOW CLEAR FLOOR SPACES ON PLANS AND |
| | COMPLY W/REQS.OF FEDERAL FAIR HOUSING |
| | ACT 24 CFR 100.205. |
| | |
| | SHT.DAPT-A7.05-MAX.DISTANCE TO BOTTOM OF |
| | WOOD BLOCKING ABOVE LIP OF TUB SHALL BE |
| | 6" PER FHA REQ.#6,FIGURE #4. |