| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | PROVISO: | | | | | | 1) AC-7 AND AC-6 UNITS SERVING CORRIDORS | | | TO HAVE FAN SHUT DOWN BY DUCT SMOKE | | | DETECTORS PER 1997 SMC 406.2RECIRCULA- | | | TING FANS SERVING AREAS USED FOR EGRESS | | | 2) OVERFLOW PROTECTION REQUIRED FOR | | | ALL A/C UNITS | | | 3) RISERS WHICH ARE SUBJECT TO MOISTURE | | | SHALL BE LINED WITH SUITABLE MATERIAL | | | TO PREVENT DETERIORATION OF DRYWALL | | | ENCLOSURE PER LOCAL AMENDMENTS 610.1.3.2 |
|