| Plan Review Notes For Permit 00040910 |
| Permit Number |
00040910 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | PLAN REFERS TO SHT.274A-3.THIS SHEET IS | | | NOT INCLUDED IN SET. | | | | | | A CLEANOUT IS REQD.ON THE INLET AND OUT- | | | LET OF THE OIL INTERCEPTOR PER SPC | | | 1004.2. | | | | | | CONDENSATE DRAINS CANNOT DISCHARGE TO | | | STORM SYSTEM INSIDE BUILDING.DRAINS | | | SHALL INDIRECTLY CONNECT TO SYSTEM ON | | | EXTERIOR OF BUILDING OR RUN INDEPENDENT | | | TO APPROVED POINT OF DISPOSAL.SMC SEC. | | | 304.8.3. | | | | | | 8"STORM DRAIN CANNOT DRAIN 18000 SQ.FT. | | | OF ROOF AREA AT 2% PER SPC TABLE 1108.2. | | | REVISE SLOPE OR INCREASE PIPE SIZE. |
|