Plan Review Notes
Plan Review Notes For Permit 00040910
Permit Number 00040910
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00PLAN REFERS TO SHT.274A-3.THIS SHEET IS
 NOT INCLUDED IN SET.
  
 A CLEANOUT IS REQD.ON THE INLET AND OUT-
 LET OF THE OIL INTERCEPTOR PER SPC
 1004.2.
  
 CONDENSATE DRAINS CANNOT DISCHARGE TO
 STORM SYSTEM INSIDE BUILDING.DRAINS
 SHALL INDIRECTLY CONNECT TO SYSTEM ON
 EXTERIOR OF BUILDING OR RUN INDEPENDENT
 TO APPROVED POINT OF DISPOSAL.SMC SEC.
 304.8.3.
  
 8"STORM DRAIN CANNOT DRAIN 18000 SQ.FT.
 OF ROOF AREA AT 2% PER SPC TABLE 1108.2.
 REVISE SLOPE OR INCREASE PIPE SIZE.