| Plan Review Notes For Permit 00040907 |
| Permit Number |
00040907 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************** UNSAT ***************** | | | | | | 1)NOTE: NOT ENOUGH ELELCTRICAL DETAIL | | | FOR REVIEW TO BE COMPLETED. | | | | | | 2)NOTE: OVER 50% OF THE ELCTRICAL WORK | | | IS BEING DONE/ YOUMUST BRING THE | | | ENTIRE HOUSE UP TO CODE. | | | | | | 3)NOTE: OUTLET SPACING PER 210-52 MUST | | | BE MET. 2`6`12` RULE. | | | | | | 4)NOTE: SMOKE DETECTOR WILL BE REQ`D | | | INSIDE AND OUTSIDE ALL SLEEPING ROOMS | | | AND ONE IN COMMON AREA. | | | | | | 5)NOTE: GFI REC`S WILL BE REQ`D BACK AND | | | FRONT OF DWELLING PER 210-52E | | | | | | 6)NOTE: NEED TO HAVE GFI OUTLET IN GAR- | | | -AGE PER 210-52 G | | | | | | 7)NOTE:OUTLET SPACING ALONG KITCHEN | | | COUNTER SPACE TO MEET 210-52-C-1 | | | | | | 7)NOTE: NEED TO SUBMIT COMPLETE LOAD | | | CALCULATIONS/SHOW IF NEW SERVICE IS | | | BEING ADDED OR EXISTING SERVICE TO RE- | | | MIAN? | | | | | | 8)NOTE: PLEASE SHOW ANY NEW A/C SYSTEMS | | | IF THEY ARE BEING INSTALLED. | | | | | | PLEASE GIVE MORE DETAIL ON WHATS EXISTIN | | | -G AND WHATS NEW? | | | | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW AND APPROVAL. IF THERE ARE | | | ANY QUESTIONS PLEASE CALL 659-8096 EXT | | | 8372 |
|