| Plan Review Notes For Permit 00040884 |
| Permit Number |
00040884 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | PROVISO: | | | 1. RE: NOTE ON SHAFT REMOVAL OR MODIFIC- | | | ATION, 1997 SMC 610.4 DUCTS EXTENDING | | | THROUGH MORE THAN ONE FLOOR TO BE PROTE- | | | CTED BY SHAFT ENCLOSURE HAVING A FIRE | | | RESITANCE NOT LESS THAN 2 HRS FOR A BUIL | | | DING 4 STORIES AND MORE IN HEIGHT. PLAN | | | UNCLEAR AS TO WHAT WILL BE CHANGED. THIS | | | CODE SHALL BE COMPLIED WITH FOR ANY | | | CHANGES. | | | 2. LOCAL AMENDMENTS REQUIRE MINIMUM 18" | | | CLEARANCE BETWEEN ROOF SURFACE AND | | | BOTTOM OF SUPPORT STRUCTURE OF STAND. | | | PLEASE UPDATE STAND PRODUCT APPROVAL, | | | PLAN INDICATES EXPIRED DADE CO. APPROVAL | | | 3. NOTE 5 AND 6 SHOW OUTSIDE AIR AND | | | EXHAUST AIR OUTLET NEXT TO EACH OTHER | | | NOTE 10 FT SEPARATION REQUIRED AS MIN- | | | IMUM. |
|