2001-01-08 00:00:00PROVISO:
 1. RE: NOTE ON SHAFT REMOVAL OR MODIFIC-
 ATION, 1997 SMC 610.4 DUCTS EXTENDING
 THROUGH MORE THAN ONE FLOOR TO BE PROTE-
 CTED BY SHAFT ENCLOSURE HAVING A FIRE
 RESITANCE NOT LESS THAN 2 HRS FOR A BUIL
 DING 4 STORIES AND MORE IN HEIGHT. PLAN
 UNCLEAR AS TO WHAT WILL BE CHANGED. THIS
 CODE SHALL BE COMPLIED WITH FOR ANY
 CHANGES.
 2. LOCAL AMENDMENTS REQUIRE MINIMUM 18"
 CLEARANCE BETWEEN ROOF SURFACE AND
 BOTTOM OF SUPPORT STRUCTURE OF STAND.
 PLEASE UPDATE STAND PRODUCT APPROVAL,
 PLAN INDICATES EXPIRED DADE CO. APPROVAL
 3. NOTE 5 AND 6 SHOW OUTSIDE AIR AND
 EXHAUST AIR OUTLET NEXT TO EACH OTHER
 NOTE 10 FT SEPARATION REQUIRED AS MIN-
 IMUM.