| Plan Review Notes For Permit 00040884 |
| Permit Number |
00040884 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) THE SECOND FLOOR PLAN ON PAGE E-1 | | | IS WHAT TYPE OF OCCUPANCY. WHAT IS | | | THE SQUARE FOOTAGE. | | | 2) DESCRIBE OPENING AT CURVED STAIR | | | AT OPENING INTO BUILDING TO THE WEST | | | AT THE SECOND LEVEL. | | | 3) NO FIRE SPRINKLERS SHOWN ON FOURTH | | | FLOOR. | | | 4) NO SMOKE DETECTION EQUIPMENT SHOWN | | | ON THE FOURTH FLOOR. | | | 5) PROVIDE COMPLETE FIRE ALARM SYSTEM | | | SHOP DRAWINGS FOR FIRE ALARM EQUIPMENT | | | SHOWN ON THE PLANS. | | | 6) THE SINGLE MEANS OF EGRESS IS NOT | | | PERMITTED FROM THE LIVE WORK LOFT | | | PER BUILDING CODE REQUIREMENTS. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|