Plan Review Notes
Plan Review Notes For Permit 00040867
Permit Number 00040867
Review Stop P
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00THE MINIMUM REQUIRED PLUMBING FIXTURES
 SHALL COMPLY W/TABLE 407 OF THE SPC.THE
 NUMBER OF FIXTURES IN THE WOMEN'S REST-
 ROOM ARE INSUFFICIENT ACCORDING TO THE
 NOTED HABITABLE SQUARE FOOT AREA OF THE
 SPACE.
  
 THE SIZE OF THE HANDICAP TOILET STALLS
 DO NOT COMPLY W/FACBC SEC.4.17.3.SEE
 EXCEPTION:NEW CONSTRUCTION.THE LAVATORY
 CANNOT INFRINGE ON THE CLEAR FLOOR
 SPACE FOR THE WATER CLOSET.
  
 URINAL SHALL BE MOUNTED AT 17"MAX.TO THE
 RIM,NOT THE BOTTOM OF THE URINAL.FACBC
 4.18.
  
 A CLEANOUT IS REQD.IN THE UPSTREAM END
 OF THE BUILDING DRAIN PER SPC SEC.710.2
  
 NOTE:SHT.P-1-THE SQUARE FOOTAGE PER
 PERSON FOR THIS OCCUPANCY PER TABLE 407
 OF THE SPC IS 200 SQ.FT.THE CODE SEC.
 403.1 OF THE SPC YOU REFERENCED ON THE
 PLAN REFERS TO THE CLEANING OF PLUMBING
 FIXTURES,NOT THE OCCUPANT LOAD.MY
 CALCULATIONS SHOW 29,465 SQ.FT.WHICH
 EQUALS AN OCCUPANT LOAD OF 148 PERSONS.
 (CALCULATIONS ARE FROM HABITABLE FLOOR
 SPACE SHOWN ON A-2.)