2001-01-08 00:00:00SHOW SQ.FOOTAGE OF HABITABLE FLOOR SPACE
 ON PLANS TO ENSURE COMPLIANCE W/SPC
 TABLE 407 FOR MIN.PLUMBING FIXTURE REQS.
  
 LAVATORIES ARE REQUIRED IN THE
 ACCESSIBLE STALLS PER FLA.ACCESS.CODE
 FOR BUILDING CONSTRUCTION SEC.4.17.3.
 RESTROOMS SHALL FULLY COMPLY W/FACBC
 OCT.1997 EDITION.
  
 SHOW INSIDE CLEAR DIMENSIONS (LXW) OF
 ACCESSIBLE STALLS AND STANDARD STALLS.
 COMPLY W/FACBC 4.17.3.,FIG.#30, SPC SEC.
 403.4.
  
 SHT.A-4-ACCESSIBLE WATER CLOSET SHALL BE
 18"FROM WALL,NOT 36" AS SHOWN PER FACBC
 FIGURE 30.
  
 SHOW HEIGHT OF URINAL.COMPLY W/FACBC SEC
 4.18.
  
 MIN.CLEAR FLOOR SPACE UNDER DRINKING
 FOUNTAIN SHALL BE 27"PER FACBC SEC.4.15.
  
 WATER HEATER SHALL BE READILY ACCESSIBLE
 PER SPC SEC.501.7.SUPPLY FIXED LADDER
 OR RELOCATE WATER HEATER TO FLOOR.
  
 WATER SUPPLY CONTROL SHALL COMPLY W/SPC
 SEC.610.4.1,610.4.2.
  
 SHOW REQD.WHEELCHAIR TURNING SPACE IN
 RESTROOMS PER FACBC SEC.4.2.3.