| Plan Review Notes For Permit 00040867 |
| Permit Number |
00040867 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | SHOW SQ.FOOTAGE OF HABITABLE FLOOR SPACE | | | ON PLANS TO ENSURE COMPLIANCE W/SPC | | | TABLE 407 FOR MIN.PLUMBING FIXTURE REQS. | | | | | | LAVATORIES ARE REQUIRED IN THE | | | ACCESSIBLE STALLS PER FLA.ACCESS.CODE | | | FOR BUILDING CONSTRUCTION SEC.4.17.3. | | | RESTROOMS SHALL FULLY COMPLY W/FACBC | | | OCT.1997 EDITION. | | | | | | SHOW INSIDE CLEAR DIMENSIONS (LXW) OF | | | ACCESSIBLE STALLS AND STANDARD STALLS. | | | COMPLY W/FACBC 4.17.3.,FIG.#30, SPC SEC. | | | 403.4. | | | | | | SHT.A-4-ACCESSIBLE WATER CLOSET SHALL BE | | | 18"FROM WALL,NOT 36" AS SHOWN PER FACBC | | | FIGURE 30. | | | | | | SHOW HEIGHT OF URINAL.COMPLY W/FACBC SEC | | | 4.18. | | | | | | MIN.CLEAR FLOOR SPACE UNDER DRINKING | | | FOUNTAIN SHALL BE 27"PER FACBC SEC.4.15. | | | | | | WATER HEATER SHALL BE READILY ACCESSIBLE | | | PER SPC SEC.501.7.SUPPLY FIXED LADDER | | | OR RELOCATE WATER HEATER TO FLOOR. | | | | | | WATER SUPPLY CONTROL SHALL COMPLY W/SPC | | | SEC.610.4.1,610.4.2. | | | | | | SHOW REQD.WHEELCHAIR TURNING SPACE IN | | | RESTROOMS PER FACBC SEC.4.2.3. |
|