| Plan Review Notes For Permit 00040867 |
| Permit Number |
00040867 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ************** UNSAT ******************* | | | | | | 1)NOTE: NEED TO SHOW THE REQ`D OUTLETS | | | FOR SHOW WINDOWS AS PER 210-62 | | | REVISE PANEL SCHEDULE. | | | | | | 2)NOTE: NEED TO SUBMIT THE LOAD CALCS | | | SHOWING ALL CONTINUOUS LOADS AT 125% | | | THIS WOULD BE LIGHTING OR ANY OTHER LOAD | | | EXPECTED TO RUN FOR 3 OR MORE HOURS PER | | | ART;22-3-B-7 AND 210-20 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATIONFOR | | | REVIEW. PLANS WOULD HAVE PASSED WITH | | | PROVISO BUT THEY WERE COMING BACK FOR | | | OTHER COMMENTS. IF THERE ARE ANY QUEST- | | | -IONS PLEASE CALL 659-8096 EXT 8372 |
|