| Plan Review Notes For Permit 00040838 |
| Permit Number |
00040838 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | SHT.A-5-SUBMIT DETAIL OF SCUPPERS.SHOW | | | DIMENSIONS(LXW) AND CALCULATIONS.COMPLY | | | W/APPENDIX "A" OF SPC. | | | | | | SHT.S-4-SHOW TERMINATION PT.OF 4"DRAIN | | | FROM OZONE CONTACT POINT. | | | | | | SHT.M-9-SHOW TERMINATION POINT OF FLOOR | | | DRAINS IN POTASSIUM PERMANGANATE AREA. | | | | | | A BACKFLOW PREVENTION DEVICE SHALL BE | | | INSTALLED ON EACH POTABLE WATER SUPPLY | | | TO EACH BUILDING PER SPC SEC.606.1.601.6 | | | | | | INDICATE BUILDING OCCUPANCY ON PLAN PER | | | SBC AMENDED COUNTY CODE SEC,301.2,301.3. | | | | | | INDICATE OCCUPANT LOAD ON PLANS FOR THE | | | PLANT.SHOW LOCATION,TYPE AND NUMBER OF | | | SANITARY FACILITIES FOR PLANT PERSONNEL. | | | SPC 407.1.3. |
|