Plan Review Notes
Plan Review Notes For Permit 00040838
Permit Number 00040838
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00SHT.A-5-SUBMIT DETAIL OF SCUPPERS.SHOW
 DIMENSIONS(LXW) AND CALCULATIONS.COMPLY
 W/APPENDIX "A" OF SPC.
  
 SHT.S-4-SHOW TERMINATION PT.OF 4"DRAIN
 FROM OZONE CONTACT POINT.
  
 SHT.M-9-SHOW TERMINATION POINT OF FLOOR
 DRAINS IN POTASSIUM PERMANGANATE AREA.
  
 A BACKFLOW PREVENTION DEVICE SHALL BE
 INSTALLED ON EACH POTABLE WATER SUPPLY
 TO EACH BUILDING PER SPC SEC.606.1.601.6
  
 INDICATE BUILDING OCCUPANCY ON PLAN PER
 SBC AMENDED COUNTY CODE SEC,301.2,301.3.
  
 INDICATE OCCUPANT LOAD ON PLANS FOR THE
 PLANT.SHOW LOCATION,TYPE AND NUMBER OF
 SANITARY FACILITIES FOR PLANT PERSONNEL.
 SPC 407.1.3.