Plan Review Notes
Plan Review Notes For Permit 00040835
Permit Number 00040835
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001- PAGE E-4 SHOWS ALL DIFFERENT KINDS OF
 CHEMICALS PLEASE LIST EACH THAT IS
 SHOWN AND SIGN OFF THAT EACH ONE IS
 NOT A CHEMICAL THAT SHOULD BE LISTED
 AS A HAZARD PER NFPA 471 AND 479
  
 2- PAGE E-6 STORAGE TANK AREA SHOWS NO
 OUTLET FOR SERVICING THE UNITS.
  
 3- PAGE E-8 ARE ANY OF THESE CHEMICALS
 A HAZARD?
  
 4- PAGE E-10 SUB STATION D1 SHOWS THE
 SERVICE TO BE 4160V TO 208Y/120 BUT
 PANEL OR DISTRIBUTION IS LISTED AT
 480V?
  
 5- PLEASE ADDRESS THE CHEMICAL ISSUE
 ASAP AND I CAN PROVISO THE OTHER ITEM