Plan Review Notes
Plan Review Notes For Permit 00040810
Permit Number 00040810
Review Stop E
Sequence Number 2
Notes
Date Text
2001-06-13 00:00:00************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT THERE ARE NO
 CONDUCTOR SIZES /OR CONDUIT FROM METER
 CAN TO MAIN AND FROM MAIN TO PANEL.
  
 2) PLEASE CLARIFY EQUIPMENT GROUNDING
 METHOD BETWEEN FIRST MEANS OF DISCONNECT
 AND PANEL(S). EQUIPMENT GROUNDING
 CONDUCTORS ARE TO BE SIZED BY 250-122.
  
 3)NOTE: PLEASE NOTE THAT LOCATION OF
 SERVICE EQUIPMENT IS NOT SHOWN ON PLANS
 PLEASE SHOW.
  
 4)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 PLEASE NOTE THAT AIC RATING WAS SHOWN
 FOR PANEL BUT NOT FOR MAIN?
 PLEASE SHOW. IF FUSED, PLEASE GIVE AIC
 OF FUSES.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372