| Plan Review Notes For Permit 00040810 |
| Permit Number |
00040810 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-07-03 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 00040810 | | | 1156 CLARE AVENUE | | | PHONE 659-0019 | | | | | | 1)- IMPACT FEES TO BE PAID TO THE | | | COUNTY BEFORE THE PERMIT CAN BE ISSUED. | | | | | | 2)- THESE PLANS SHOW IN THE TITLE BLOCK | | | THAT THEY WERE PREPARED BY ARCH. M. | | | CORBITT, THEY NEED THE ARCH. OF RECORD | | | TO SIGN & SEAL PLANS, THAT ARE TO BE FOR | | | PUBLIC RECORD. | | | | | | 3)- MISSING ARE THEPRODUCT REPORTS FOR | | | DOORS, WINDOWS & ROOFING MATERIALS. DADE | | | COUNTY OR SBCCI REPORT ARE ACCEPTED. | | | SBC 1606.4.1 AMEND/ 1707.4.1. | | | | | | 4)_ SBC 104.2 SHOW AN INTERIOR PARTITION | | | CONSTRUCTION DETAIL. | | | | | | 5)- THE PROPOSED BUILDING IS LOCATED IN | | | A FIRE ZONE, SHOW THE FIRE DESIGN NUMBER | | | FOR THE EXTERIOR WALLS, WALLS WILL | | | REQUIRE A 2 HR RATING. | | | | | | 6)- SBC 1503.1.2.3. SHOW HOW ROOF DRAIN- | | | AGE WILL OCCUR? | | | | | | 7)- SBC 1804.2 AMEND. SOILS REPORT RE- | | | QUIRED. | | | | | | 8)- HANDICAPPED RAMP DOESN'T COMPLY WITH | | | THE RAMP RISE & RUN. CHECK THE FINISH | | | FLOOR HEIGTH OF 15.8' FLOOR ELEVATION | | | TO THE 10.10' AT THE ACCESS RAMP. ALSO | | | HOW DO WE ACCOMPLISH GETTING TO THE LIFT | | | ? DETAILS ON THE LIFT AS WELL AS THE | | | SECOND FLOOR LANDING. | | | | | | 9)- SBC 1606.2.4 (MWFRS) INDICATE ON THE | | | PLAN THE WIND PRESSURE ZONES FOR THE | | | OPENINGS, WALLS & ROOF. | | | | | | JIM WITMER | | | BUILDING PLAN REVIEW | | | (561) 659-8096 EX 8412 |
|