Plan Review Notes
Plan Review Notes For Permit 00040810
Permit Number 00040810
Review Stop E
Sequence Number 1
Notes
Date Text
2001-04-02 00:00:00******************* UNSAT ************
  
 1)NOTE: PLEASE NOTE THAT PER LOCAL CODE
 OUTLET SPACINGTO MEET COUNTYWIDE AND C
 ITY WIDE ART;210-50. FOR STORAGE AND/OR
 OFFICE.
  
 2)NOTE: PLEASE PLACE ALL BRANCH CIRCUIT
 #`S ON PLANS AND CORRLATE WITH PANEL
 SCHEDULES. PLEASE SUBMIT PANEL SCHEDULES
 215-5
  
 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 4) PLEASE NOTE MISSING OUTLET FOR A/C
 EQUIPMENT PER 210-63 OF NEC AND 309.1
 MECHANICAL CODE.
  
 5)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 215-5
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372