Plan Review Notes
Plan Review Notes For Permit 00040810
Permit Number 00040810
Review Stop B
Sequence Number 1
Notes
Date Text
2001-03-27 00:00:00PROPERTY IS IN FLOOD ZONE A9 BFE 13.0
 PROVIDE CERTIFICATION ON APPROPRIATE
 FEMA FORM
  
 PROVIDE ENERGY CODE CALCULATIONS.
  
 IMPACT FEES MUST BE PAID TO THE COUNTY,
 CALL 233-5025 FOR MORE INFORMATION.
  
 PLANS ARE REQUIRED TO BE SIGNED, SEALED
 AND DATED BY THE ARCHITECT.
  
 PROVIDE PRODUCT APPROVALS FORE THE
 DOORSAND ROOF COVERING.
  
 SHOW AN INTERIOR PARTITION DETAIL.
  
 SHOW THE FIRE DESIGN NUMBER FOR THE
 REQUIRED 2 HR RATED EXTERIOR WALLS.
  
 SHOW THE METHOD OF ROOF DRAINAGE.SEE
 SBC 1503.1.2.3.
  
 A SOIL INVESTIGATIION IS REQUIRED.SEE
 SBC 1804..2 AS AMENDED BY THE CITY.
  
 SHOW THE HC CURB CUTS TO COMPLY WITH 4.7
 OF THE FACBC.
  
 SHOW HOW THE C AND D COLUMNS PENETRATE
 THE SECOND FLOOR.
  
 SHOW HOW THE HC LIFT WILL TERMINATE AT
 THE SECOND FLOOR.
  
 SHOW THE CODES AND STANDARDS USED FOR
 THE DESIGN.INCLUDING EDITION.
  
 PROVIDE A SKETCH OF THE WIND ZONES AND
 THEIR PRESSURES FOR THE WALLS AND ROOF.