Plan Review Notes
Plan Review Notes For Permit 00040803
Permit Number 00040803
Review Stop R
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00THE STRUCTURE NEEDS TO BE DESIGNED
 ACCORDING TO SBC 1997 OR ASCE 7 95.THE
 WIND ANALYSIS UPLIFT REPORT STATES ASCE
 7 88 WAS USED. RECALCULATE USING ONE OF
 THE ABOVE DESIGN CRITERIA,1606 SBC 1997
  
 PROVIDE PRODUCT APPROVAL FOR THE FRENCH
 DOORS PREPARED BY A RECONIZED AGENCY.
 IN LIEW OF THE ABOVE PROVIUDE SITE
 SPECIFIC ENGINEERING BEARING A ORIGINAL
 SIGNATURE AND RAISED SEAL.
  
 THE PROPOSED GAGRAGE DOOR IS NOT DESIGNE
 D TO WITHSTAND THE WIND PRESSURES.
  
 METRO DADE PRODUCT APPROVAL FOR THE
 OUTSWING DOOR, INCLUDE THE DRAWINGS
 SPECIFIED IN SECTION PARA 2.1.NOTE WE
 DO NOT ACCEPT BROWARD COUNTY PRODUCT
 APPROVAL FORMS.
  
 NEEDS COUNTY IMP[ACT FEES PAID.
  
 SEE MECHANICAL REVIEW COMMENTS.
  
 ***************************************
 6/28/00PLANS STILL NOT DESIGNED TO
 REQUIRED DESIGN CRITERIA, ASCE 7-95
 AND 145 MPH WIND ZONE*****
 PROVIDE DESIGN COMPLIANCE FORM AND
 CALCULATIONS USED FOR DETERMING THE WIND
 PRESSURES FOR THE EXTERIOR WINDOW
 OPENINGS WHICH ARE LOCATED IN THE END
 ZONES. ALSO INCLUDE WIND LOAD CALCULATIO
 FOR THE OVERHEAD GARAGE DOOR OPENINGS.
 **************************************