2001-01-08 00:00:00**************** UNSAT *****************
  
 1)NOTE: PLEASE SHOW THE REQ`D DEDICATED
 BATH(S) CIRCUIT(S) PER 210-11-C-3. THEY
 MUST BE 20 AMP #12 AWG. PLEASE LIST ON
 PANLEL SCHEDULE.
  
 2)NOTE: PLEASE SUBMIT THE AIC RATING FOR
 THE MAINS. MAINS AND ALL PANEL/BREAKER
 EQUIPMENT MUST BE RATED FOR THE
 AVAILABLE FAULT CURRENT. THIS WILL BE
 REQ`D ON ALL PLANS FOR REVIEW. 110-9/
 215-5
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372