| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE SHOW THE REQ`D DEDICATED | | | BATH(S) CIRCUIT(S) PER 210-11-C-3. THEY | | | MUST BE 20 AMP #12 AWG. PLEASE LIST ON | | | PANLEL SCHEDULE. | | | | | | 2)NOTE: PLEASE SUBMIT THE AIC RATING FOR | | | THE MAINS. MAINS AND ALL PANEL/BREAKER | | | EQUIPMENT MUST BE RATED FOR THE | | | AVAILABLE FAULT CURRENT. THIS WILL BE | | | REQ`D ON ALL PLANS FOR REVIEW. 110-9/ | | | 215-5 | | | | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL 659-8096 EXT 8372 |
|