| Plan Review Notes For Permit 00040803 |
| Permit Number |
00040803 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | TRUSS PLAN REVIEW : DENIED | | | TIA ANCHOR LEGEND "L" 1170 UPLIFT VS | | | TRUSS PLAN R2/ 1320 UPLIFT. | | | GT4 2M ARCH PLAN R1 =(2M) VS TRUSS PLAN | | | PAGE 76 R13690. R2 MTS12 ALLOWABLE 860 | | | (PINE)X 3=2580 VS TRUSS PLAN R2=3665. | | | GT6 3M DIFFERENCES FROM THE ARCH PLAN,IF | | | THE TRUSS MANUFACTURER CHANGES THE LAY | | | OUT WITHOUT WRITTEN PERMISSION THE TRUSS | | | CO BECOMES RESPONSIBLE FOR ALL ANCHORAGE | | | DETAILS FROM THE BEARING TO THE FOOTER. | | | NOTED ON PLAN.WHAT TYPE OF CONNECTORS? | | | ALSO CRUSHING VALUES, 3 1/2X 550 LB=8661 | | | PAGE 104 R1=9796 /R2=8661 VS 9354. | | | NOTE ARCH BLOCK WALL VS LEDGER TYPE OF | | | CONNECTION? WALL TO TRUSS = ARCH. TRUSS | | | TO TRUSS OR GIRDER TO TRUSS= TRUSS ENG | | | TO DESIGN.LIST TYPES OF HANGERS TO BE | | | USED,BE SPECIFIC. | | | ARCH PLAN LIST "M" 1845 UPLIFT ON THE | | | FOLLOWING TRUSSES, T44,T46,T48,T50,T52, | | | T54,T56& H58. THE UPLIFT VALUES RANGE | | | FROM 3290 TO 2672, PAGES 24-29 TRUSS PL. |
|