2001-01-08 00:00:00TRUSS PLAN REVIEW : DENIED
 TIA ANCHOR LEGEND "L" 1170 UPLIFT VS
 TRUSS PLAN R2/ 1320 UPLIFT.
 GT4 2M ARCH PLAN R1 =(2M) VS TRUSS PLAN
 PAGE 76 R13690. R2 MTS12 ALLOWABLE 860
 (PINE)X 3=2580 VS TRUSS PLAN R2=3665.
 GT6 3M DIFFERENCES FROM THE ARCH PLAN,IF
 THE TRUSS MANUFACTURER CHANGES THE LAY
 OUT WITHOUT WRITTEN PERMISSION THE TRUSS
 CO BECOMES RESPONSIBLE FOR ALL ANCHORAGE
 DETAILS FROM THE BEARING TO THE FOOTER.
 NOTED ON PLAN.WHAT TYPE OF CONNECTORS?
 ALSO CRUSHING VALUES, 3 1/2X 550 LB=8661
 PAGE 104 R1=9796 /R2=8661 VS 9354.
 NOTE ARCH BLOCK WALL VS LEDGER TYPE OF
 CONNECTION? WALL TO TRUSS = ARCH. TRUSS
 TO TRUSS OR GIRDER TO TRUSS= TRUSS ENG
 TO DESIGN.LIST TYPES OF HANGERS TO BE
 USED,BE SPECIFIC.
 ARCH PLAN LIST "M" 1845 UPLIFT ON THE
 FOLLOWING TRUSSES, T44,T46,T48,T50,T52,
 T54,T56& H58. THE UPLIFT VALUES RANGE
 FROM 3290 TO 2672, PAGES 24-29 TRUSS PL.