| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | DENIED | | | | | | 1)PROVIDE ENERGY CALCS AND METHOD OF | | | COMPLIANCE PER FL ENERGY CODE FOR NEW | | | ADDITION,IF EXISTING RESIDENCE HAS | | | CENTRAL A/C OR HEAT;SHOW LOCATION AND | | | SIZES OF EXISTING SUPPLIES AND RETURN | | | | | | 2)PROVIDE 2 CURRENT COPIES OF SBCCI OR | | | METRO-DADE PRODUCT APPROVALS FOR WINDOWS | | | DOORS AND STORM PANELS | | | | | | 3)PROVIDE INSTALLATION SCHEDULE AND KEY | | | PLAN WITH SPECIFIC ANCHORS TO BE USED | | | FOR STORM PANELS | | | | | | 4)PROVIDE DEMOLITION AND STRUCTURAL | | | DETAILS AND ANALYSIS FOR SECTION OF | | | EXISTING TO BE REMOVED | | | | | | 5)PAGE 4 OF THE PLANS SHOW RAFTERS @ 16" | | | CENTERS; THE NOTES CALL FOR ROOF TRUSSES | | | WITH SIMPSON STRAP ANCHORS ON 24"CENTERS | | | SPECIFY WHICH TYPE OF ROOF CONSTRUCTION | | | WILL BE USED AND HOW IT WILL BE ATTACHED | | | ;PROVIDE ROOF FRAMING PLAN |
|