2001-01-08 00:00:00DENIED
  
 1)PROVIDE ENERGY CALCS AND METHOD OF
 COMPLIANCE PER FL ENERGY CODE FOR NEW
 ADDITION,IF EXISTING RESIDENCE HAS
 CENTRAL A/C OR HEAT;SHOW LOCATION AND
 SIZES OF EXISTING SUPPLIES AND RETURN
  
 2)PROVIDE 2 CURRENT COPIES OF SBCCI OR
 METRO-DADE PRODUCT APPROVALS FOR WINDOWS
 DOORS AND STORM PANELS
  
 3)PROVIDE INSTALLATION SCHEDULE AND KEY
 PLAN WITH SPECIFIC ANCHORS TO BE USED
 FOR STORM PANELS
  
 4)PROVIDE DEMOLITION AND STRUCTURAL
 DETAILS AND ANALYSIS FOR SECTION OF
 EXISTING TO BE REMOVED
  
 5)PAGE 4 OF THE PLANS SHOW RAFTERS @ 16"
 CENTERS; THE NOTES CALL FOR ROOF TRUSSES
 WITH SIMPSON STRAP ANCHORS ON 24"CENTERS
 SPECIFY WHICH TYPE OF ROOF CONSTRUCTION
 WILL BE USED AND HOW IT WILL BE ATTACHED
 ;PROVIDE ROOF FRAMING PLAN