Plan Review Notes
Plan Review Notes For Permit 00040637
Permit Number 00040637
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00************** UNSAT ******************
 OK ON 7/5/00 DV PALMER
 1)NOTE: PLEASE SUBMIT AIC RAINGS OF
 MAINS/PANEL. MAINS MUST BE RATED FOR THE
 AVAILABLE FAULT CURRENT. 110-9/215-5
  
 2)NOTE: PLEASE NOTE THAT SMOKE DETECTORS
 ARE REQ`D INSIDE AND OUTSIDE ALL SLEEP-
 -ING ROOMS IN NEW DWELLINGS.,
 NFPA-72 2-2.1.1.1
  
 3)NOTE: PLEASE SEE 210-52 FOR OUTLET
 SPACING OF WALL SPACE.
  
 4)NOTE: PLEASE SEE 210-8-A-6. ALL OUTLET
 -S SERVING KITCHEN COUNTERSPACE ARE TO
 BE GFI/GFI PROTECTED. PLEASE SHOW
  
 5)NOTE: PLEASE LIST ON PANEL SCHEDULE,
 THE REQ`D DEDICATED BATH(S) CIRCUIT(S)
 BY 210-11-C-3.MUST BE 20 AMP AND #12
  
 6)NOTE: PLEAS SHOW THE REQ`D A/C CU DISC
 PER 440-11/215-5
  
 7)NOTE:PLEASE SEE YOUR NOTES. YOU SHOW
 1994 NEC? WE ARE NOW IN THE '99' NEC.
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372