| Plan Review Notes For Permit 00040637 |
| Permit Number |
00040637 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ************** UNSAT ****************** | | | OK ON 7/5/00 DV PALMER | | | 1)NOTE: PLEASE SUBMIT AIC RAINGS OF | | | MAINS/PANEL. MAINS MUST BE RATED FOR THE | | | AVAILABLE FAULT CURRENT. 110-9/215-5 | | | | | | 2)NOTE: PLEASE NOTE THAT SMOKE DETECTORS | | | ARE REQ`D INSIDE AND OUTSIDE ALL SLEEP- | | | -ING ROOMS IN NEW DWELLINGS., | | | NFPA-72 2-2.1.1.1 | | | | | | 3)NOTE: PLEASE SEE 210-52 FOR OUTLET | | | SPACING OF WALL SPACE. | | | | | | 4)NOTE: PLEASE SEE 210-8-A-6. ALL OUTLET | | | -S SERVING KITCHEN COUNTERSPACE ARE TO | | | BE GFI/GFI PROTECTED. PLEASE SHOW | | | | | | 5)NOTE: PLEASE LIST ON PANEL SCHEDULE, | | | THE REQ`D DEDICATED BATH(S) CIRCUIT(S) | | | BY 210-11-C-3.MUST BE 20 AMP AND #12 | | | | | | 6)NOTE: PLEAS SHOW THE REQ`D A/C CU DISC | | | PER 440-11/215-5 | | | | | | 7)NOTE:PLEASE SEE YOUR NOTES. YOU SHOW | | | 1994 NEC? WE ARE NOW IN THE '99' NEC. | | | | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL 659-8096 EXT 8372 |
|