Plan Review Notes
Plan Review Notes For Permit 00040577
Permit Number 00040577
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00**************** PROVISO ***************
  
 1)NOTE: YOU SHOW THE AIC RATINGS OF THE
 ELEC. PANELS. THIS IS FINE AND IS REQ`D,
 BUT NEED TO SUBMIT THE AIC RATING OF THE
 MAIN DISCONNECT. 110-9 215-5 MAIN MUST B
 RATED FOR THE AVAILABLE FAULT CURRENT.
  
 2)NOET : PLEASE VERIFY ANY SHOW WINDOW
 RECEPTS THAT BE BE REQ`D BY 210-62 AND
 SHOW ON PLANS.
  
 3)NOTE:PLEASE INDICATE THE GROUNDING
 REQ`D FOR THE TELEPHONE BOARD.
  
 4)NOTE: PLEASE NOTE AS PER 110-26 THE
 WORKING CLEARANCES AROUND THE ELECTRICAL
 PANELS. YOU SHOW THE TRANSFORMER RIGHT
 IN FRONT?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW BEFORE ANY ROUGH ELECTRICAL
 INSPECTION IS CALLED IN. IF THERE ARE
 ANY QUESTIONS PLEASE CALL 561-659-8096
 EXT 8372