| 2001-01-08 00:00:00 | CHECKLIST: |
| | 1-SURVEY; |
| | -PROFESSIONAL ENGINEER SHOULD NOT SEAL |
| | ORIGINAL DOCUMENTS. SEC 61G15-23.002 |
| | FLORIDA BOARD OF PROFESSIONAL ENGINEER |
| | 2-PROVIDE PRODUCT APPROVAL FOR BUTT |
| | GLAZING ASSEMBLY, FIREPLACE, ENTRY- |
| | DOORS ("INSWING"). |
| | -SLIDING GLASS DOORS PRODUCT APPROVAL |
| | DOESN'T WORK FOR THIS HOUSE. SEE DWG 1 |
| | OF 6 OF SGD PRODUCT APPROVAL AND SIZE |
| | OF DOORS IN ARCHITECTURAL DRAWINGS. |
| | 3-ENGINEER TO SIGN, SEAL AND DATE DWGS |
| | WITH THE EXTERIOR ELEVATIONS ALSO. |
| | ALL DRAWINGS SHALL BEAR THE NAME AND |
| | SIGNATURE OF THE PERSON RESPONSIBLE |
| | FOR THE DESIGN. SECTION 104.2.1 OF |
| | CITY AMENDMENTS. |
| | 4-PROVIDE COMPLETE INSTALLATION DETAIL |
| | FOR AHU IN ATTIC. SPECIFY FASTENERS. |
| | SECTION 104.2.2 CITY AMENDMENTS. |
| | 5-PROVIDE ATTIC ACCESS AT MAIN ROOF AND |
| | SPECIFY SIZE OF ATTIC ACCESS AT GARAGE |
| | SECTION 2309.6 SBC 1997. |
| | 6-PROVIDE SAFETY GLASS. SEE PLANS FOR |
| | COMMENTS. SECTION 2405.2 SBC 1997. |
| | 7-REVISE SIZE OF CEILING FANS. SEE TABLE |
| | 6-6 OF FLORIDA ENERGY CODE, 1997 ED. |
| | 8-PROVIDE COPIES OF THE SOIL TESTS |
| | RESULTS DONE AS PER SECTION 1804.2.7.3 |
| | CITY AMENDMENTS. |
| | 9-OWES $669.73 FOR LOW VALUATION FOR |
| | CONSTRUCTION AND RADON FEES. |
| | 10-PAY IMPACT FEES TO PALM BEACH COUNTY. |
| | BRING STAMPED DRAWINGS AND RECEIPT. |
| | |
| | NOTES: |
| | 1-SEE COMMENTS BY OTHER TRADES. |
| | 2-REVISE ALL PLANS AS REQUIRED AND BRING |
| | THIS SET OF MARKED DRAWINGS IN ORDER |
| | TO EXPEDITE THE REVIEW PROCESS. |