2001-01-08 00:00:00***************** UNSAT ****************
  
 1)NOTE: YOU HAVE NOTED ON RISER DIAGRAM
 TO USE CURRENT LIMITING FUSES?? BUT YOU
 ARE SHOWING A MAIN BRKR PANEL? PLEASE
 CORRECT.IF THERE IS GOING TO BE A FUSED
 DISCONNECT THEN PLEASE SHOW.
 PLEASE PROVIDE THE AIC RATING OF PANELS,
 MAIN DISC, OR FUSES. 215-5 AND 110-9
  
 2)NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED. AS REQ`D BY 210-8-A-6.
  
 3)NOTE; PLEAS EINCLUDE BLDG. STEEL AS
 PART OF THE GROUNDING ELECTRODE SYSTEM
 AS PER 250-50./215-5
  
 4)NOTE: PLEASE INCLUDE THE REQ`D DEDICAT
 -ED BATH(S) CIRCUIT(S) ON PANEL SCHEDULE
 ASPER 210-11-C-3
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS PLEAS
 -E CALL 659-8096 EXT 8372