| 2001-01-08 00:00:00 | SECOND CHECKLIST: |
| | 1-SURVEY: |
| | PROFESSIONAL ENGINEER SHOULD NOT SEAL |
| | ORIGINAL DOCUMENTS. SEC 61G15-23.002. |
| | 2-PROVIDE PRODUCT APPROVAL FOR BUTT |
| | GLAZING ASSEMBLY, FIREPLACE, INSWING |
| | ENTRY DOORS. |
| | -SLIDING GLASS DOORS PRODUCT APPROVAL |
| | DOESN'T QUALIFY FOR THE SIZE OF DOORS |
| | SHOWN ON PLANS AND ELEVATIONS. |
| | 3-ENGINEER TO SIGN, SEAL AND DATE DWGS |
| | WITH THE EXTERIOR ELEVATIONS. THEY |
| | SHOW THE DESIGN PRESSURES CALCULATED |
| | FOR THIS BUILDING. |
| | 4-PROVIDE COMPLETE INSTALLATION DETAIL |
| | FOR AHU IN ATTIC. SPECIFY ALL |
| | FASTENERS. SEC 104.2.2 CITY AMENDMENTS |
| | 5-PROVIDE SAFETY GLASS AT BEDROOM #2. |
| | SECTION 2405.2 SBC 1997. |
| | 6-REVISE SIZE OF CEILING FANS. SEE TABLE |
| | 6-6 OF FLORIDA ENERGY EFFICIENCY CODE |
| | FOR BUILDING CONSTRUCTION, 1997 ED. |
| | 7-PROVIDE COPIES OF THE SOIL TESTS |
| | RESULTS DONE AS PER SECTION 1804.2.7.3 |
| | OF CITY AMENDMENTS TO SBC 1997. |
| | 8-OWES $669.73 FOR LOW VALUATION AND |
| | RADON FEES. (RECEIPT TO PAY ATTACHED) |
| | 9-PAY IMPACT FEES TO PALM BEACH COUNTY. |
| | BRING STAMPED DRAWINGS AND RECEIPT. |
| | 10-CLARIFY WHY ORIGINAL DRAWING A-1 WAS |
| | NOT REVISED. INSTEAD A REVERSED PLAN |
| | WAS SUBMITTED AND NOT MATCHING THE |
| | OTHER PLANS. |
| | 11-SEE COMMENTS ON PLANS AND UPDATE/ |
| | REVISE AS REQUIRED. |
| | -SEE ROOF TRUSS PLAN FOR COMMENTS. |
| | |
| | |
| | NOTES: |
| | 1-SEE COMMENTS BY OTHER TRADES. |
| | 2-PLEASE RETURN REVIEWED SET AFTER |
| | CORRECTIONS ARE DONE IN ORDER TO |
| | EXPEDITE THE REVIEW PROCESS. |