| Date |
Text |
| 2001-01-08 00:00:00 | CHECKLIST: |
| | 1-SURVEY: |
| | -PROFESSIONAL ENGINEER SHOULD NOT SEAL |
| | ORIGINAL DOCUMENTS. SEC 61G15-23.002 |
| | FLORIDA BOARD OF PROFESSIONAL ENGINEER |
| | 2-PROVIDE PRODUCT APPROVAL FOR BUTT |
| | GLAZING ASSEMBLY, FIREPLACE, ENTRY |
| | DOORS (INSWING). |
| | -SLIDING GLASS DOORS PRODUCT APPROVAL |
| | DOESN'T MEET THE SIZE OF SLIDING DOORS |
| | SHOWN ON PLANS AND ELEVATIONS. |
| | 3-ENGINEER TO SIGN, SEAL AND DATE DWGS |
| | WITH THE EXTERIOR ELEVATIONS ALSO. |
| | ALL DRAWINGS SHALL BEAR THE NAME AND |
| | SIGNATURE OF THE PERSON RESPONSIBLE |
| | FOR THE DESIGN. SECTION 104.2.1 OF |
| | CITY AMENDMENTS. |
| | 4-PROVIDE COMPLETE INSTALLATION DETAIL |
| | FOR AHU IN ATTIC. SPECIFY FASTENERS. |
| | SECTION 104.2.2 CITY AMENDMENTS. |
| | 5-PROVIDE ATTIC ACCESS AT MAIN ROOF AND |
| | SPECIFY SIZE OF ATTIC ACCESS AT GARAGE |
| | SECTION 2309.6 SBC 1997. |
| | 6-PROVIDE SAFETY GLASS AT BEDROOM #2 AND |
| | MASTER BATH. SECTION 2405.2 SBC 1997. |
| | 7-REVISE SIZE OF CEILING FANS. SEE TABLE |
| | 6-6 OF FLORIDA ENERGY CODE, 1997 ED. |
| | 8-PROVIDE COPIES OF THE SOIL TEST |
| | RESULTS DONE AS PER SECTION 1804.2.7.3 |
| | CITY AMENDMENTS. |
| | 9-OWES $669.73 FOR LOW CONSTRUCTION |
| | VALUATION AND RADON FEES. |
| | 10-PAY IMPACT FEES TO PALM BEACH COUNTY. |
| | BRING STAMPED DRAWINGS AND RECEIPT. |
| | |
| | NOTES: |
| | 1-SEE COMMENTS BY OTHER TRADES. |
| | 2-REVISE ALL ORIGINAL PLANS AS REQUIRED. |