Plan Review Notes
Plan Review Notes For Permit 00040247
Permit Number 00040247
Review Stop R
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00DENIED
  
 1)ENERGY CODE COMPLIANCE FORMS MUST BE
 SIGNED BY OWNER/AGENT.
  
 2)DESIGN CERTIFICATION FORM LISTS MEAN
 ROOF HEIGHT OF 12'2" ARCHITECTURAL
 DRAWINGS SHOW M.R.HGT. OF 19'9". PLEASE
 CORRECT.
  
 3)SHEET A-6 OF ARCHITECTURAL DRAWINGS
 REFRENCE ASCE7-88 THE CORRECT REFRENCE
 STANDARD FOR THE 97 STANDARD BUILDING
 CODE IS ASCE7-95. PLEASE CORRECT.
  
 4)REVISED ARCHITECTURAL DRAWING SHEET
 A-8 MUST BE EMBOSSED WITH A RAISED SEAL.
  
 5)PROVIDE SOIL BEARING TEST REPORT PRIOR
 TO FIRST INSPECTION.
  
 6)PROVIDE 2 COPIES OF KEY PLAN AND
 INSTALLATION SCHEDULE SPECIFING SPECIFIC
 ANCHORS TO BE USED FOR STORM PANELS,
 PRIOR TO FIRST INSPECTION.
  
 7)PROVIDE 2 CURRENT COPIES OF METRO-DADE
 OR SBCCI PRODUCT APPROVALS FOR ALL
 EXTERIOR WINDOWS AND DOORS TO BE USED.
 SPECIFICALLY OUTSWING EXT. DOUBLE DOORS,
 OUTSWING DOUBLE DOORS WITH SIDELITES,1HR
 FIRE RATED GLASS BLOCK,6FT & 16FT GARAGE
 DOORS AND OUTSWING SINGLE GLASS PANEL
 DOORS.
  
 8)PALM BEACH COUNTY IMPACT FEES MUST BE
 PAID TO THE COUNTY, THE PLANS STAMPED BY
 THEM AND A COPY OF THE RECEIPT SUBMITTED
 TO THE CITY BLDG. DEPT. BEFORE A PERMIT
 TO CONSTRUCT CAN BE ISSUED.