Plan Review Notes
Plan Review Notes For Permit 00040247
Permit Number 00040247
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00*************** UNSAT *****************
  
 NOTES GIVEN ON THESE SAME THINGS ON PRE-
 VIOUS PLANS
  
 1)NOTE: SMOKE DETECTORS ARE REQ`D INSIDE
 AND OUTSIDE ALL SLEEPING ROOMS.
 NFPA-72 2-2.1.1.1
  
 2)NOTE:MISSING THE REQ`D OUTLET INFRONT
 OF DWELLING AS PER 210-52E
  
 3)NOTE: MISSING OUTLET PER 210-52
 IN BEDROOM. 2`,6`,12` RULE
  
 4)NOTE: PLEASE LABEL ALL OUTLETS SERVING
 KITCHEN COUNTER SPACE AS GFI/GFI PROTECT
 -ED. AS PER 210-8-A-6
  
 5)NOTE:PLEASE LIST ON PANEL SCHEDULE THE
 REQ`D BATH(S) CIRCUIT #12,20 AMP
 AS PER 210-11-C-3
  
 6(NOTE" PROVIDE AIC RATING FOR MAINS
 AND FOR PANELS. PER 110-9 AND 215-5
 MAINS MUST BE RATED FOR THE AVAILABLE
 FAULT CURRENT.
  
 7)NOTE: PLEASE INCLUDE BLDG. STEEL AS
 PART OF THE GROUNDING ELECTRODE SYSTEM
 AS REQ`D BY 250-50.
  
 PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW . IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372