| Plan Review Notes For Permit 00040247 |
| Permit Number |
00040247 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************** UNSAT ***************** | | | | | | NOTES GIVEN ON THESE SAME THINGS ON PRE- | | | VIOUS PLANS | | | | | | 1)NOTE: SMOKE DETECTORS ARE REQ`D INSIDE | | | AND OUTSIDE ALL SLEEPING ROOMS. | | | NFPA-72 2-2.1.1.1 | | | | | | 2)NOTE:MISSING THE REQ`D OUTLET INFRONT | | | OF DWELLING AS PER 210-52E | | | | | | 3)NOTE: MISSING OUTLET PER 210-52 | | | IN BEDROOM. 2`,6`,12` RULE | | | | | | 4)NOTE: PLEASE LABEL ALL OUTLETS SERVING | | | KITCHEN COUNTER SPACE AS GFI/GFI PROTECT | | | -ED. AS PER 210-8-A-6 | | | | | | 5)NOTE:PLEASE LIST ON PANEL SCHEDULE THE | | | REQ`D BATH(S) CIRCUIT #12,20 AMP | | | AS PER 210-11-C-3 | | | | | | 6(NOTE" PROVIDE AIC RATING FOR MAINS | | | AND FOR PANELS. PER 110-9 AND 215-5 | | | MAINS MUST BE RATED FOR THE AVAILABLE | | | FAULT CURRENT. | | | | | | 7)NOTE: PLEASE INCLUDE BLDG. STEEL AS | | | PART OF THE GROUNDING ELECTRODE SYSTEM | | | AS REQ`D BY 250-50. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION | | | FOR REVIEW . IF THERE ARE ANY QUESTIONS | | | PLEASE CALL 659-8096 EXT 8372 |
|