2001-01-08 00:00:00************** UNSAT ******************
  
 1)NOTE: PLEASE SHOW ALL BRANCH CIRCUT
 #`S ON PLANS FOR ALL LIGHTING AND OUTLET
 -S.
  
 2)NOTE: SHOW LIGHTING THAT PERMIT APPL.
 SAYS THAT YOU ARE INSTALLING.
  
 3)NOTE: PROVIDE LOAD CALCULATION ON
 EXISTING MAIN TO BLDG.? BEFORE YOU CAN
 ADD NEW MAIN. ALSO SHOW WIRE SIZE FOR
 NEW PANEL/ MAIN, CONDUIT SIZE ETC.
  
 4)NOTE:PLEASE SUBMIT NEW LOAD CALC ON
 NEW PANEL AND PANEL SCHEDULE.
  
 5)NOTE: PLEASE PROVIDE AIC RATING OF
 EQUIPMENT MAINS. MAINS MUST BE RATED TO
 HANDLE THE AVAILABLE FAULT CURRENT.
 110-9/215-5
  
 6)NOTE: PLEASE SHOW A MORE DETAIL LAYOUT
 OF THE SERVICE AND THE TENANT SPACES
 AND WHERE EACH SERVICE FOR EACH TENANT -
 IS BEING SEPARATED BY FIRE WALLS.
 MAINS MUST BE GROUPED AND LABELED 1OF3,
 2OF 3,ETC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372