| Plan Review Notes For Permit 00040172 |
| Permit Number |
00040172 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ************** UNSAT ****************** | | | | | | 1)NOTE: PLEASE SHOW ALL BRANCH CIRCUT | | | #`S ON PLANS FOR ALL LIGHTING AND OUTLET | | | -S. | | | | | | 2)NOTE: SHOW LIGHTING THAT PERMIT APPL. | | | SAYS THAT YOU ARE INSTALLING. | | | | | | 3)NOTE: PROVIDE LOAD CALCULATION ON | | | EXISTING MAIN TO BLDG.? BEFORE YOU CAN | | | ADD NEW MAIN. ALSO SHOW WIRE SIZE FOR | | | NEW PANEL/ MAIN, CONDUIT SIZE ETC. | | | | | | 4)NOTE:PLEASE SUBMIT NEW LOAD CALC ON | | | NEW PANEL AND PANEL SCHEDULE. | | | | | | 5)NOTE: PLEASE PROVIDE AIC RATING OF | | | EQUIPMENT MAINS. MAINS MUST BE RATED TO | | | HANDLE THE AVAILABLE FAULT CURRENT. | | | 110-9/215-5 | | | | | | 6)NOTE: PLEASE SHOW A MORE DETAIL LAYOUT | | | OF THE SERVICE AND THE TENANT SPACES | | | AND WHERE EACH SERVICE FOR EACH TENANT - | | | IS BEING SEPARATED BY FIRE WALLS. | | | MAINS MUST BE GROUPED AND LABELED 1OF3, | | | 2OF 3,ETC. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL 659-8096 EXT 8372 |
|