Plan Review Notes
Plan Review Notes For Permit 00040162
Permit Number 00040162
Review Stop R
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00CHECKLIST:
 1-DESIGNER, ARTHUR L PATTERSON, IS NOT
 AN ARCHITECT OR ENGINEER. THEREFORE,
 HE DOESN'T QUALIFY TO FILL OUT AND
 SIGN AND SEAL THE DESIGN CERTIFICATION
 FOR BUILDING CODE COMPLIANCE FORM
 (CHAPTER 471 AND 481 FLORIDA STATUTES)
 -CITY AMENDMENTS SECTION 104.2.3 ALLOWS
 OTHER PERSON OTHER THAN AN ARCHITECT
 OR ENGINEER TO PROVIDE DESIGN SERVICES
 PROVIDED THAT THE ENTIRE DWELLING
 CONFORMS TO A PRESCRIPTIVE STANDARD.
 THE CITY HAS ADOPTED THE STANDARD FOR
 HURRICANE RESISTANT RESIDENTIAL
 CONSTRUCTION, KNOWN AS SSTD 10-97, AS
 THE PRESCRIPTIVE STANDARD.
 -USE THE SSTD 10-97 GUIDELINES TO
 DESIGN THE FOUNDATION, SHOW THE
 ENDWALLS AND SIDEWALLS, SHEARWALLS,
 CALCULATE THE UPLIFT LOADS, SHOW THE
 CONTINUITY OF VERTICAL WALL REINFORCE-
 MENT, SPECIFY TIE BEAMS AND LINTELS,
 REINFORCEMENT AT ENDS OF OPENINGS AND
 CORNERS.
 NOTE: ALL THIS INFORMATION CAN BE
 IN CHAPTER 2 OF SSTD 10-97.
 2-EGRESS WINDOWS FROM MASTER BEDROOM AND
 BEDROOM BEHIND THE MASTER BATHROOM
 DON'T COMPLY WITH THE MINIMUM SIZE
 REQUIREMENTS OF SECTION 1005.4.4 OF
 SBC 1997.
 3-CLARIFY IF THE HOUSE HAS CENTRAL AIR
 CONDITIONING OR NOT. IF SO, CLARIFY
 HOW IS THE ADDITION GOING TO BE AIR
 CONDITIONED. PROVIDE PLANS AND SPECS.
 4-HOW IS THE MASTER BATHROOM GOING TO BE
 VENTILATED? SECTION 1203.4.2 SBC 1997.
 5-PROVIDE COMPLETE BUCK DETAILS FOR
 EXTERIOR DOOR AND WINDOWS. SECTION
 104.2.2 CITY AMENDMENTS TO SBC 1997.
 6-PROVIDE TYPICAL WALL SECTION SHOWING
 REINFORCEMENT AROUND WINDOW OPENINGS
 IN ORDER TO RECEIVE THE INSTALLATION
 OF STORM PANELS. SECTION 104.2.2 CITY
 AMENDMENTS TO SBC 1997.
 7-PROVIDE COMPLETE INFORMATION FOR
 STORM PANELS.
 8-CLARIFY CONNECTION OF NEW WOOD TRUSSES
 TO EXISTING TIE BEAM. HOW ARE THE TWO
 CONNECTORS SPECIFIED IN THE WALL
 SECTION GOING TO BE NAILED TO THE TIE
 BEAM. SEC 104.2.2 CITY AMENDMENTS.
 NOTE: THIS ARE WOOD TO WOOD CONNECTORS
 NOT WOOD TO CONCRETE.
 9-PROVIDE COMPLETE ROOF FRAMING PLAN
 INDICATING TRUSSES SIZE AND BLOCKING
 AND BRIDGING REQUIRED. SEC 104.2.2 OF
 CITY AMENDMENTS TO SBC 1997.
 10-SEE COMMENTS ON PLANS AND REVISE AND
 UPDATE DRAWINGS AS REQUIRED.
 NOTE: RETURN REVIEWED DRAWINGS TO
 EXPEDITE THE REVIEW PROCESS.
 11-PROVIDE PRODUCT APPROVAL FOR EXTERIOR
 DOOR AND WINDOWS, SINGLE PLY ROOFING
 SYSTEM.
  
  
 NOTE: SEE COMMENTS BY ELECTRICAL AND
 MECHANICAL PLAN REVIEWERS.