2001-01-08 00:00:00************** UNSAT******************
  
 1)NOTE: PLEASE SUBMIT COMPLETE LOAD
 CALCULATION FOR EXISTING SERVICE.AS REQ`
 -D BY 220-3-C-1
  
 2)NOTE: PLEASE SUBMIT NEW PANEL SCHEDULE
 FOR MAIN PANEL. PLEASE INCLUDE THE DED-
 -ICATED CIRCUTS FOR BATH(S) AS PER
 210-11-C-3
  
 3)NOTE:PLEASE SHOW THE REQ`D OUTLET FOR
 REAR OF DWELLING AS PER 210-52E
  
 4)NOTE: MORE OUTLETS ARE REQ`D IN NEW
 ADDITION AREA PER 210-52 2`,6`,12` RULE
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372