Notes
Date Text
2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-PROVIDE PRODUCT APPROVAL FOR ENTRY
 DOORS, FRENCH DOOR AT MASTER SUITE.
 -DRAWINGS IN PRODUCT APPROVAL FOR
 FRENCH DOOR AT MASTER SUITE ARE NOT
 LEGIBLE.
 2-STORM PANELS:
 PROVIDE A COMPLETE INSTALLATION SCHED.
 AS PER CITY SAMPLE ATTACHED.
 -PANELS #13 AND #14 EXCEED THE MAXIMUM
 SPAN OF 12'-4".
 -SHEET 4 OF 5: CLEARLY INDICATE ANCHORS
 AND SPACING TO BE USED ACCORDING TO
 THE STRUCTURE TYPE, CONNECTION TYPE
 AND DESIGN PRESSURES.
 -SHEET 3 OF 5: DESIGN PRESSURE ARE
 MARKED INCORRECTLY. SEE ARCHITECT'S
 PLANS FOR CALCULATED DESIGN PRESSURES.
 3-CLARIFY WHO IS THE STRUCTURAL ENGINEER
 OF RECORD. THE DESIGN CERTIFICATION
 FOR BUILDING CODE COMPLIANCE FORM
 IS SIGNED BY AN ENGINEER, BUT THIS
 ENGINEER DIDN'T SIGN, SEAL AND DATE
 THE STRUCTURAL DRAWINGS.
 4-THE MEAN ROOF HEIGHT SPECIFIED IN THE
 ENGINEERED ROOF TRUSSES IS NOT THE
 SAME AS THE ONE SPECIFIED IN THE
 DESIGN CERTIFICATION FOR BUILDING CODE
 COMPLIANCE FORM. REVISE AS REQUIRED.
 NOTE: MEAN ROOF HEIGHT IS TAKEN FROM
 GRADE, NOT FROM FINISH FLOOR, TO THE
 AVERAGE POINT OF THE HIGHEST ROOF.