| Plan Review Notes For Permit 00040056 |
| Permit Number |
00040056 |
|
| Review Stop |
R |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | APPROVED WITH PROVISO: | | | 1-PROVIDE ROOF FRAMING PLAN SHOWING THE | | | CALCULATED UPLIFT LOADS AND ANCHOR | | | SCHEDULE. SEC 104.2.2 CITY AMENDMENTS. | | | 2-REVISE THE DESIGN CERTIFICATION FOR | | | BUILDIONG CODE COMPLIANCE FORM. THE | | | MEAN ROOF HEIGHT IS 23'-0" PLUS OR | | | MINUS, NOT 20'-0". MEAN ROOF HEIGHT IS | | | TAKEN FROM GRADE, NOT FROM FINISH | | | FLOOR, TO THE AVERAGE POINT OF THE | | | HIGHEST ROOF. | | | 3-PRODUCT APPROVALS: | | | -PROVIDE PRODUCT APPROVAL FOR GOLFCART | | | GARAGE DOOR. | | | -PROVIDE PRODUCT APPROVAL FOR "INSWING" | | | ENTRY DOORS. | | | 4-CLARIFY SIZE OF FOOTING F-1. SHEET #1 | | | SPECIFIES 18"X18" FOOTING, BUT SHEET | | | #6 (WALL SECTION) SPECIFIES A 20"X18" | | | FOOTING. | | | 5-PROVIDE COMPLETE SETS OF ENGINEERED | | | ROYAL WALL PANELS SHOWING THE CONCRETE | | | THICKNESS AND REINFORCEMENT. SIGNED, | | | SEALED AND DATED. | | | SECTION 104.2.2 CITY AMENDMENTS. |
|