Date Text
2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-PROVIDE ROOF FRAMING PLAN SHOWING THE
 CALCULATED UPLIFT LOADS AND ANCHOR
 SCHEDULE. SEC 104.2.2 CITY AMENDMENTS.
 2-REVISE THE DESIGN CERTIFICATION FOR
 BUILDIONG CODE COMPLIANCE FORM. THE
 MEAN ROOF HEIGHT IS 23'-0" PLUS OR
 MINUS, NOT 20'-0". MEAN ROOF HEIGHT IS
 TAKEN FROM GRADE, NOT FROM FINISH
 FLOOR, TO THE AVERAGE POINT OF THE
 HIGHEST ROOF.
 3-PRODUCT APPROVALS:
 -PROVIDE PRODUCT APPROVAL FOR GOLFCART
 GARAGE DOOR.
 -PROVIDE PRODUCT APPROVAL FOR "INSWING"
 ENTRY DOORS.
 4-CLARIFY SIZE OF FOOTING F-1. SHEET #1
 SPECIFIES 18"X18" FOOTING, BUT SHEET
 #6 (WALL SECTION) SPECIFIES A 20"X18"
 FOOTING.
 5-PROVIDE COMPLETE SETS OF ENGINEERED
 ROYAL WALL PANELS SHOWING THE CONCRETE
 THICKNESS AND REINFORCEMENT. SIGNED,
 SEALED AND DATED.
 SECTION 104.2.2 CITY AMENDMENTS.