| Plan Review Notes For Permit 00040050 |
| Permit Number |
00040050 |
|
| Review Stop |
R |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | APPROVED WITH PROVISO: | | | 1-PROVIDE ROOF FRAMING PLAN SHOWING THE | | | CALCULATED UPLIFT LOADS AND ANCHOR | | | SCHEDULE. SEC. 104.2.2 CITY AMENDMENTS | | | 2-REVISE THE DESIGN CERTIFICATIONFOR | | | BUILDING CODE COMPLIANCE. MEAN ROOF | | | HEIGHT IS 23'-6" PLUS OR MINUS, NOT | | | 20'-0". MEAN ROOF HEIGHT IS TAKEN FROM | | | GRADE, NOT FROM FINISH FLOOR, TO THE | | | AVERAGE POINT OF THE HIGHEST ROOF. | | | 3-PRODUCT APPROVALS: | | | -PROVIDE PRODUCT APPROVAL FOR GOLFCART | | | GARAGE DOOR. | | | -FRENCH DOOR PRODUCT APPROVAL: DRAWINGS | | | ARE NOT LEGIBLE. | | | -PROVIDE PRODUCT APPROVAL FOR "INSWING" | | | ENTRY DOORS. | | | 4-CLARIFY SIZE OF FOOTING F-1. SHEET 1 | | | SAYS 18"X18" AND SHEET 6 SAYS 20"X18". | | | 5-PROVIDE COMPLETE SET OF ENGINEERED | | | ROYAL WALL PANELS SHOWING ALL CONCRETE | | | THICKNESS AND REINFORCEMENT. SIGNED, | | | SEALED AND DATED. | | | SECTION 104.2.2 CITY AMENDMENTS. |
|