Plan Review Notes
Plan Review Notes For Permit 00040022
Permit Number 00040022
Review Stop P
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00THE MINIMUM REQUIRED NUMBER OFSANITARY
 FACILITIES SHALL COMPLY W/TABLE 407 OF
 1994 EDITION OF SPC.PRESENTLY THERE ARE
 INSUFFICIENT FACILITIES.SEE SPC SECTION
 407.1.3.FOR ALLOWED DEDUCTIBLE AREAS.
  
 SINK IN LOUNGE SHALL BE HANDICAP ACCESS-
 IBLE AND COMPLY W/FACBC SEC.4.24.1-
 4.24.7.
  
 WATER HEATER SHALL BE READILY ACCESSIBLE
 PER SPC SEC.501.7.SUPPLY A PERMANENT
 FIXED LADDER OR RELOCATE TO FLOOR.
  
 INSTALLATION OF VENTS ON FLOOR DRAINS
 AND MOP SINK SHALL COMPLY W/SPC SEC.
 906.2.1.
  
 DRINKING FOUNTAIN SHALL COMPLY W/FACBC
 SEC.4.1.3.(10)(A).PROVISIONS SHALL BE
 MADE FOR PEOPLE WHO HAVE TROUBLE BENDING
 OR STOOPING.
  
 FLOOR DRAINS SHALL BE EQUIPPED W/TRAP
 PRIMERS PER SPC SEC.409.4.1.1.
  
 WIDTH OF H.C. STALL SHALL COMPLY W/FACBC
 SEC/4.17.3.FIXTURE CLEARANCE OF LAV.
 SHALL COMPLY W/SPC SEC.403.1,403.4.