| Plan Review Notes For Permit 00040022 |
| Permit Number |
00040022 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | THE MINIMUM REQUIRED NUMBER OFSANITARY | | | FACILITIES SHALL COMPLY W/TABLE 407 OF | | | 1994 EDITION OF SPC.PRESENTLY THERE ARE | | | INSUFFICIENT FACILITIES.SEE SPC SECTION | | | 407.1.3.FOR ALLOWED DEDUCTIBLE AREAS. | | | | | | SINK IN LOUNGE SHALL BE HANDICAP ACCESS- | | | IBLE AND COMPLY W/FACBC SEC.4.24.1- | | | 4.24.7. | | | | | | WATER HEATER SHALL BE READILY ACCESSIBLE | | | PER SPC SEC.501.7.SUPPLY A PERMANENT | | | FIXED LADDER OR RELOCATE TO FLOOR. | | | | | | INSTALLATION OF VENTS ON FLOOR DRAINS | | | AND MOP SINK SHALL COMPLY W/SPC SEC. | | | 906.2.1. | | | | | | DRINKING FOUNTAIN SHALL COMPLY W/FACBC | | | SEC.4.1.3.(10)(A).PROVISIONS SHALL BE | | | MADE FOR PEOPLE WHO HAVE TROUBLE BENDING | | | OR STOOPING. | | | | | | FLOOR DRAINS SHALL BE EQUIPPED W/TRAP | | | PRIMERS PER SPC SEC.409.4.1.1. | | | | | | WIDTH OF H.C. STALL SHALL COMPLY W/FACBC | | | SEC/4.17.3.FIXTURE CLEARANCE OF LAV. | | | SHALL COMPLY W/SPC SEC.403.1,403.4. |
|