Plan Review Notes
Plan Review Notes For Permit 00040022
Permit Number 00040022
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00*************DENIED*********************
  
 1) PROVIDE OUTSIDE AIR CALCULATIONS PER
 UNIT PER ASHRAE 62-89
 2) PROVIDE AIR BALANCE CALCULATIONS TO
 SHOW COMPLIANCE WITH 1997 SMC 501.2
 3) AHU #5 SUPPY AIR OVER DESIGN AMOUNT
 4) AHU #1 SHOWS ONE DIFFUSER WITH NO
 AMOUNT CFM DESIGNED
 5) AHU #3 AND FC-1 SHOWS NO RETURN AIR
 6) ROOF MOUNTED CONDENSING UNIT NEEDS
 DETAIL OF STANDS AND MOUNTING METHOD.
 NOTE: LOCAL CODE REQUIRES MIN. 18" OF
 CLEARANCE BETWEEN ROOF SURFACE AND
 BOTTOM OF SUPPORT BEAM OF STAND
  
 PROVIDE ABOVE INFROMATION FOR REVIEW OF
 THIS PROJECT