| Plan Review Notes For Permit 00040022 |
| Permit Number |
00040022 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************DENIED********************* | | | | | | 1) PROVIDE OUTSIDE AIR CALCULATIONS PER | | | UNIT PER ASHRAE 62-89 | | | 2) PROVIDE AIR BALANCE CALCULATIONS TO | | | SHOW COMPLIANCE WITH 1997 SMC 501.2 | | | 3) AHU #5 SUPPY AIR OVER DESIGN AMOUNT | | | 4) AHU #1 SHOWS ONE DIFFUSER WITH NO | | | AMOUNT CFM DESIGNED | | | 5) AHU #3 AND FC-1 SHOWS NO RETURN AIR | | | 6) ROOF MOUNTED CONDENSING UNIT NEEDS | | | DETAIL OF STANDS AND MOUNTING METHOD. | | | NOTE: LOCAL CODE REQUIRES MIN. 18" OF | | | CLEARANCE BETWEEN ROOF SURFACE AND | | | BOTTOM OF SUPPORT BEAM OF STAND | | | | | | PROVIDE ABOVE INFROMATION FOR REVIEW OF | | | THIS PROJECT |
|