| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************** PROVISO *************** | | | | | | 1)NOTE: YOU SHOW ON SHEET E-1 TWO SETS | | | OF 350 MCIL. THIS IS CORRECT. YOU CANNOT | | | USE THE TAP RULE. THESE ARE THE MAIN | | | FEEDERS. PLEASE THE CONDUCTOR SIZES YOU | | | SHOW ON E-1. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW BEFORE ANY ROUGH ELECTRICAL | | | INSPECTION IS CALLED IN. IF THERE ARE | | | ANY QUESTIONS PLEASE CALL 659-8096 X8372 |
|