Notes
Date Text
2001-01-08 00:00:00************** UNSAT *******************
  
 1)NOTE: SHEET E-2 YOU SHOW GROUNDING
 ELECTRODE GOING TO GROUND RING AROUND
 EQUIPMENT. THIS IS FINE BUT YOU ALSO
 NEED GROUNDING ELECTRODE CONDUCTOR
 GOING TOO BLDG. STEEL AND CONCRETE REBAR
 AS REQ`D BY 250-50 OF THE '99' NEC.
 PLEASE SHOW GOING TO THOSE LOCATIONS.
 215-5.
  
 2)NOTE: ALSO PLEASE INCLUDE ANY METERCAN
 OR METER CT`S ON PLANS.215-5
  
 3)NOTE: YOU SHOW A 600 AMP DISC WITH 600
 AMP OVERCURRENT PROTECTION FOR 500 MCM
 WIRE. OVERCURRENT PROTECTION NEEDS TO BE
 AT 400 AMPS. 310-16
  
 4)NOTE: YOU SHOW THE AIC RATING OF THE
 400 AMP CONTROL PANEL BUT NEED TO SUBMIT
 THE AIC RATINGOF MAIN DISC. 110-9
 215-5 MAIN MUST BE RATED FOR THE
 AVAILABLE FAULT CURRENT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW.IF THERE ARE ANY QUESTIONS PLEASE
 CALL 659-8096 EXT 8372