| Plan Review Notes For Permit 00031785 |
| Permit Number |
00031785 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE SHOW SMOKE DETECTORS | | | INSDIE AND OUTSIDE ALL SLEEPING ROOMS. | | | AS REQ`D BY NFPA-72 2-2.1.1.1 | | | | | | 2)NOTE: PLEASE CHECK KITCHEN COUNTER- | | | SPACE REQ`MENTS 210-52-C-1 | | | | | | 3)NOTE: PLEASE SUBMIT THE ELECTRICAL | | | SERVICE. YOU SHOW LOAD CALCULATION BUT | | | NOT THE SERVICE. 215-5 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION | | | FOR REVIEW . IF THERE ARE ANY QUESTIONS | | | PLEASE CALL 659-8096 EXT 8372 |
|