| Plan Review Notes For Permit 00031741 |
| Permit Number |
00031741 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************** UNSAT ****************** | | | | | | 1)NOTE: YOU SHOW THE SMOKE DETECTORS ON | | | THE SAME CIRCUIT WITH THE BATH GFI`S. | | | THIS IS NOT PERMITTED. 210-11-C-3 | | | BATH(S) ARE DEDICATED. | | | | | | 2)NOTE: ALSO MISSING SMOKE DETECTOR | | | OUTSIDE BEDROOM. IF THE DEN/BEDROOM IS | | | GIVEN AS OPTIONAL BEDROOM THEN SD`S ARE | | | REQ`D INSIDE AND OUTSIDE. | | | | | | | | | 3)NOTE:PANEL SCHEDULE SHOWS TWO SM APP- | | | -LIANCE CIRCUITS.THIS DOES NOT CORRELATE | | | WITH PLANS? THE LIGHTING IS SHOWN AS | | | ONE OF THE CIRCUITS?? PLEASE CORRECT. | | | | | | 4)NOTE: THE NOTESON THE LEFTHAND SIDE | | | OF THE PLANS REFERENCE CODES FROM THE | | | '96' NEC. PLEASE CORRECT CODE #`S TO | | | REFLECT '99' NEC. | | | | | | 5)NOTE:PLEASE SUBMIT AND HAVE DRAWN ON | | | MAIN/PANEL THE AIC RATING OF THE MAIN | | | BREAKER. MAIN MUST BE RATED FOR THE | | | AVAILABLE FAULT CURRENT PER 110-9/215-5 | | | AIC RATINGS ARE FIGURED FROM FAULT | | | CURRENT CALCULATIONS. | | | | | | | | | PLEASE CORRECT AND SUBMIT ALL THE ABOVE | | | INFORMATION FOR REVIEW. IF THERE ARE ANY | | | QUESTIONS PLEASE CALL 659-8096 EXT 8372 |
|