Plan Review Notes
Plan Review Notes For Permit 00031723
Permit Number 00031723
Review Stop R
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00THE DESIGN COMPLIANCE FORM STATES THE
 INCORRECT BASIC VELOCITY PRESSURES FOR
 A MEAN ROOF HEIGHT OF 16 FEET.
 SBC 1997 SECTION 1606
  
 PLAN #2 NEEDS ENGINEER RAISED SEAL &
 SIGNATURE.
  
 PLAN #2, BUILDING INFORMATION PARAGRAPH
 STATES THAT ASCE 7-88 AS A DESIGN
 CRITERIA. NOTE THIS IS A INVALID CRITER-
 IA AND CAN NOT MIX DESIGN CRITERIA. THE
 DESIGN FORM ON PLAN #1 STATES SBC 1606
 WAS USED.RECALCULATE WIND PRESSURES.
  
 PLAN #2 TRUSS CONNECTOR & ANCHOR
 SCHUDULE ALSO STATES ASCE 7-88. SEE
 ABOVE COMMENT.
  
 NOTE DO NOT CROSS OUT OR MAKE CORRECTION
 ON PLAN #2. PROVIDE A NEW PLAN.