| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | THE DESIGN COMPLIANCE FORM STATES THE | | | INCORRECT BASIC VELOCITY PRESSURES FOR | | | A MEAN ROOF HEIGHT OF 16 FEET. | | | SBC 1997 SECTION 1606 | | | | | | PLAN #2 NEEDS ENGINEER RAISED SEAL & | | | SIGNATURE. | | | | | | PLAN #2, BUILDING INFORMATION PARAGRAPH | | | STATES THAT ASCE 7-88 AS A DESIGN | | | CRITERIA. NOTE THIS IS A INVALID CRITER- | | | IA AND CAN NOT MIX DESIGN CRITERIA. THE | | | DESIGN FORM ON PLAN #1 STATES SBC 1606 | | | WAS USED.RECALCULATE WIND PRESSURES. | | | | | | PLAN #2 TRUSS CONNECTOR & ANCHOR | | | SCHUDULE ALSO STATES ASCE 7-88. SEE | | | ABOVE COMMENT. | | | | | | NOTE DO NOT CROSS OUT OR MAKE CORRECTION | | | ON PLAN #2. PROVIDE A NEW PLAN. |
|