| Plan Review Notes For Permit 00031708 |
| Permit Number |
00031708 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************** UNSAT ****************** | | | | | | 1)NOTE: PLANS SHOW THE SMOKE DETECTORS | | | ON THE SAM E CIRCUT WITH THE BATH GFI`S? | | | THIS IS NOT PERMITTED BY ART 210-11-C-3 | | | OF THE NEC. | | | | | | 2)NOTE: PLEASE SHOW THE REQ`D SMOKE | | | DETECTOR OUTSIDE BEDROOM #2? ALSO IF THE | | | PLEASE NOTE IF THE DEN IS MADE INTO A | | | SLEEPING ROOM THIS WILL REQ` SD ALSO. | | | | | | 3)NOTE: PLEASE SUBMIT THE AIC RATING | | | OF THE MAIN. THE MAIN MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9 | | | | | | 4)NOTE:PLEASE SHOW ON PLANS THE COLD | | | WATER PIPE AS PART OF THE GROUNDING | | | ELECTRODE SYSTEM PER 250-50/215-5 | | | | | | YOU ARE REFERENCING THE CODES FOR GROUND | | | -ING UNDER THE 96 NEC. WE ARE UNDER THE | | | 99' NEC AND THOSE CODE #`S HAVE CHANGED. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW.IF THERE ARE ANY QUESTIONS PLEASE | | | CALL 659-8096 EXT 8372 |
|