Notes
Date Text
2001-01-08 00:00:00*************** UNSAT ******************
  
 1)NOTE: PLANS SHOW THE SMOKE DETECTORS
 ON THE SAM E CIRCUT WITH THE BATH GFI`S?
 THIS IS NOT PERMITTED BY ART 210-11-C-3
 OF THE NEC.
  
 2)NOTE: PLEASE SHOW THE REQ`D SMOKE
 DETECTOR OUTSIDE BEDROOM #2? ALSO IF THE
 PLEASE NOTE IF THE DEN IS MADE INTO A
 SLEEPING ROOM THIS WILL REQ` SD ALSO.
  
 3)NOTE: PLEASE SUBMIT THE AIC RATING
 OF THE MAIN. THE MAIN MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9
  
 4)NOTE:PLEASE SHOW ON PLANS THE COLD
 WATER PIPE AS PART OF THE GROUNDING
 ELECTRODE SYSTEM PER 250-50/215-5
  
 YOU ARE REFERENCING THE CODES FOR GROUND
 -ING UNDER THE 96 NEC. WE ARE UNDER THE
 99' NEC AND THOSE CODE #`S HAVE CHANGED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW.IF THERE ARE ANY QUESTIONS PLEASE
 CALL 659-8096 EXT 8372