2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-FLOOD ZONE "AO". WILL NEED TO PROVIDE
 ELEVATION CERTIFICATE.
 2-REVISE/UPDATE ALL ORIGINAL DRAWINGS
 SHOWING THE DESIGN PRESSURES FOR
 EXTERIOR OPENINGS AS CALCULATED BY THE
 PROFESSIONAL ENGINEER OF RECORD. SHOW
 CALCULATIONS. SEE PLANS FOR COMMENTS.
 ALSO, CLEARLY WRITE NAME, ADDRESS AND
 LICENSE NUMBER OF ENGINEER ON DRAWINGS
 3-CLEARLY SPECIFY CEILING CONSTRUCTION
 AT FRONT AND BACK PORCHES. INCLUDING
 FASTENER TYPE AND SPACING. SECTION
 2504 SBC 1997.
 4-PRODUCT APPROVALS:
 -PROVIDE PRODUCT APPROVAL FOR DOUBLE
 ENTRY DOORS, WINDOW MULLIONS.PLEASE
 MAKE SURE DRAWINGS ARE LEGIBLE.
 5-NORANDEX PRODUCT APPROVALS:
 -PROFESSIONAL ENGINEER OF RECORD TO
 WRITE SITE SPECIFIC LOCATION; SPECIFY
 WHICH PRODUCTS ARE TO BE USED IN THIS
 PROJECT; CLEARLY WRITE HIS NAME,
 ADDRESS AND LICENSE NUMBER AND SIGN,
 SEAL AND DATE THIS SITE SPECIFIC
 PRODUCT APPROVAL.
 -NOTE: NEED COPIES OF TESTS RESULTS FOR
 SLIDING GLASS DOORS AS PER ASTM
 E-330. (SEC. 1706 SBC 1997).
 6-STORM PANELS:
 -PROVIDE A COMPLETE INSTALLATION SCHED.
 AND KEY PLAN (ONE SUBMITTED IS FOR
 ANOTHER MODEL) AND CLEARLY INDICATE
 MOUNTING METHOD TO BE USED; ANCHOR TO
 BE USED ACCORDING TO DESIGN PRESSURES
 (MEAN ROOF HEIGHT 15'-6" PLUS/MINUS),
 STORM PANEL SPAN, EDGE DISTANCE AND
 BUILDING CONSTRUCTION (MASONRY).
 7-SOIL TEST REPORT NEEDS ORIGINAL
 SIGNATURE AND DATE WHEN DOCUMENT IS
 SEALED.
  
 NOTE: ALL ITEMS ON PROVISO TO BE
 RE-SUBMITTED TO THIS OFFICE PRIOR
 TO CONSTRUCTION OR INSTALLATION OF
 REFERENCED ITEMS.