| Plan Review Notes For Permit 00031607 |
| Permit Number |
00031607 |
|
| Review Stop |
R |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | DENIED | | | | | | 1)FLOOD ELEVATION CERTIFICATE WILL BE | | | REQUIRED | | | | | | 2)PROVIDE 2 CURRENT COPIES OF METRO-DADE | | | OR SBCCI PRODUCT APPROVALS FOR SLIDING | | | GLASS DOORS AND HORIZONTAL SLIDING | | | WINDOWS. SITE SPECIFIC ENGINEERING THAT | | | WAS SUBMITTED IS NOT ACCEPTABLE.IT DOES | | | NOT COVER HORIZONTAL SLIDING WINDOWS AND | | | THE SLIDING GLASS DOORS TEST SUMMARIES | | | DO NOT SHOW THAT A UNIFORM STATIC AIR | | | PRESSURE TEST WAS PREFORMED (ASTM E-330) | | | THIS TEST IS FOR WINDLOADS. | | | THE SUBMITTAL FOR MUST HAVE THE SITE | | | LOCATION LISTED AND BE SIGNED,SEALED AND | | | DATED BY THE DESIGN PROFESSIONAL OF | | | RECORD. |
|