| Plan Review Notes For Permit 00031607 |
| Permit Number |
00031607 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************** UNSAT ****************** | | | | | | 1)NOTE: PLEASE SUBMIT THE AIC RATING OF | | | EQUIPMENT MAIN. MAINS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT. 110-9/215-5 | | | | | | 2)NOTE: YOU SHOW KITCHEN LIGHTING ON THE | | | SMALL APPLIANCE CIRUCIT? PLEASE CORRECT. | | | | | | 3)NOTE;AS PER 210-11-C-3 BATHS ARE TO BE | | | ON THEIR OWN! THE SMOKE DETECTORS ARE | | | NOT TO BE ON THE CIRCUIT.210-52D | | | | | | 4)NOTE: AS PER 250-50 GROUNDING ELECTROD | | | -E TO COLD WATER ASLO IF METAL. | | | | | | 5)NOTE: IN YOUR NOTES YOU ARE REF. '96' | | | NEC. PLEASE CHANGE TO REFLECTTHE | | | CODE TABLES OF THE '99' NEC. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW, IF THERE ARE ANY QUESTIONS | | | PLEASE CALL 659-8096 EXT 8372 |
|