2001-01-08 00:00:00*************** UNSAT ******************
  
 1)NOTE: PLEASE SUBMIT THE AIC RATING OF
 EQUIPMENT MAIN. MAINS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT. 110-9/215-5
  
 2)NOTE: YOU SHOW KITCHEN LIGHTING ON THE
 SMALL APPLIANCE CIRUCIT? PLEASE CORRECT.
  
 3)NOTE;AS PER 210-11-C-3 BATHS ARE TO BE
 ON THEIR OWN! THE SMOKE DETECTORS ARE
 NOT TO BE ON THE CIRCUIT.210-52D
  
 4)NOTE: AS PER 250-50 GROUNDING ELECTROD
 -E TO COLD WATER ASLO IF METAL.
  
 5)NOTE: IN YOUR NOTES YOU ARE REF. '96'
 NEC. PLEASE CHANGE TO REFLECTTHE
 CODE TABLES OF THE '99' NEC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW, IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372