Plan Review Notes
Plan Review Notes For Permit 00031584
Permit Number 00031584
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00*************** UNSAT ******************
  
 1)NOTE:SMOKE DETECTORS ARE REQ`D INSIDE
 AND OUTSIDE ALL SLEEPING ROOMS.
 AS PER NFPA-72 2-2.1.1.1
  
 2)NOTE: AS PER 210-52E ONE GFI OUTLET IS
 REQ`D BACK OF DWELLING (NEW ADDITION)
 THE LOCATION OUTBACK IS YOUR CHOICE.
  
 3)NOTE:AS PER 210-52 MISSING OUTLET IN
 MASTER BEDROOM. 2` OF WALL.
  
 4)NOTE:AS REQ`D BY ART 250-52 C MIN GRND
 ROD LENGTH IS 8` FT. PLEASE CORRECT.
  
 5)NOTE:PLEASE SHOW ON THE RISER DIAGRAM
 THE BLDG. STEEL AS PART OF THE GROUND-
 ING ELECTRODE SYSTEM. THIS IS THE STEEL
 IN THE NEW ADDITION. 250-50
  
 6)NOTE: NEED TO SUBMIT THE AIC RATING OF
 THE MAIN IN YOUR PANEL. AIC RATING FOR
 THE MIN AIC CAN BE FIGURED FROM THE
 FAULT CURRNET CALCULATIONS. 110-9/215-5
  
 7)NOTE; YOU SHOW ONCE AGAIN AN 18 POLE
 /CIRCUT PANEL? PLEASE COUNT UP THE
 NUMBER OF BRKRS AND CHANGE THE PANEL TO
 ACCOMADATE THE SPACES. 215-5
  
 8)NOTE: YOU SHOW 4500 KW FOR GEN LIGHTIN
 -G. THIS IS MORETHAN YOUR 3WATTS PER SQ.
 FT. THIS IS OK BUT PLEASE CORRECT TO
 REFLECT THE PROPER AMOUNT OF 3696.KW
  
 9)NOTE:PLEASE INCLUDE ON PANEL SCHEDULE
 THE REQ`D DEDICATED BATH CIRCUT FOR
 THE NEW MASTER BATH. AS PER 210-11-C-3
 #12 AWG AND 20 AMP.
 10)NOTE:YOU ARE SHOWING 2500WATTS FOR
 THE PUMP ON A SINGLE POLE 20AMP BRKR.??
 THIS LOAD IS TOO LARGE FOR BRKR. PLEASE
 DOUBLE CHECK THE LOAD OF PUMP AND IF IT
 IS GOING TO BE A 220V LOAD. 215-5
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTION
 PLEASE DO NOT HESITATE TO CALL.
 MY # IS 659-8096 EXT 8372