| Plan Review Notes For Permit 00031578 |
| Permit Number |
00031578 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1)FIXTURES DOWNSTREAM OF WATER CLOSETS | | | SHALL BE VENTED PER SPC SEC.913.2. | | | | | | 2)FIXTURE BRANCHES NOT PERMITTED ON WET | | | VENTS PER COUNTYWIDE AMENDMENTS TO SPC | | | SEC.911.1.1. | | | | | | 3)LAUNDRY RAY SHALL BE STACKED AND | | | VENTED PER SPC SEC.901.2. | | | | | | CALL IF YOU HAVE QUESTIONS. | | | 561-659-8096,EXT.8377. | | | | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|