| Plan Review Notes For Permit 00031578 |
| Permit Number |
00031578 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************** UNSAT ****************** | | | | | | 1)NOTE:MISSING AIC RATING OF MAIN.110-9 | | | | | | 2)NOTE: MISSING SMOKE DETECTORS INSDIE | | | ALL SLEEPING ROOMS NFPA-72 2-2.1.1.1 | | | | | | 3)NOTE:MISSING REQ`D BATH(S) CIRCUITS | | | PER 210-11-C-3 | | | | | | 4)NOTE: OUTLET SPACING TO MEET CODE | | | 210-52 | | | | | | 5)NOTE:MISSING BLDG. STEEL AS PART OF | | | THE GROUNDING ELECTRODE SYSTEM 250-50 | | | | | | 6)NOTE: PLANS SHOW MAIN DISCONNECT? BUT | | | THE ELECTRICAL RISER SHOWS MAIN BRK | | | PANEL? WHICH ONE? PLEASE CORRELATE. | | | | | | PLEASE ALL THE ABOVE FOR REVIEW. IF THER | | | E ARE ANY QUESTIONS PLEASE CALL | | | 659-8096 EXT 8372 |
|